《低壓電氣裝置 第4-41部分:安全防護(hù) 電擊防護(hù)》GB/T 16895.21-2020/IEC 60364-4-41:2017 Low-voltage electrical installations Part 4 – 41:Protection for safety –Protection against electric shock,4次提到“不超過(guò)30mA”RCD的設(shè)置要求,且均為附加防護(hù)!分別如下:
411.1 通則
Where specified, additional protection is provided by a residual current protective device (RCD) with rated residual operating current not exceeding 30 mA in accordance with 415.1.
當(dāng)有具體規(guī)定時(shí),可采用符合415.1條要求的額定剩余電流動(dòng)作值不超過(guò)30mA的剩余電流動(dòng)作保護(hù)電器(RCD)作附加防護(hù)措施。
411.3.3 用于插座和戶外移動(dòng)設(shè)備的供電更進(jìn)一步的要求
Further requirements for socket-outlets and for the supply of mobile equipment for use outdoors
Additional protection by means of a residual current protective device (RCD) with a rated residual operating current not exceeding 30 mA shall be provided for
◆a.c. socket-outlets with a rated current not exceeding 32 A that are liable to be used by ordinary persons and are intended for general use; and
◆a.c. mobile equipment for use outdoors with a rated current not exceeding 32 A.
額定動(dòng)作電流不超過(guò)30mA的剩余電流動(dòng)作保護(hù)電器(RCD)作為附加防護(hù)用于:
①供一般人員用普通用途的額定電流不超過(guò)32A的交流插座,和
②供戶外額定電流不超過(guò)32A的交流移動(dòng)式設(shè)備。
411.3.4 在TN和TT系統(tǒng)中用于照明回路的附加要求
Additional requirements for circuits with luminaires in TN- and TT-systems
In premises designed to accommodate a single household, additional protection by a residual current protective device (RCD) with a rated residual operating current not exceeding 30 mA shall be provided for a.c.final circuits supplying luminaires.
對(duì)于單獨(dú)住戶的房屋向照明供電的交流終端回路,應(yīng)提供額定剩余動(dòng)作電流不超過(guò)30mA的剩余電流動(dòng)作保護(hù)電器(RCD) 作為附加防護(hù)。
415.1.1 在交流系統(tǒng)內(nèi)裝設(shè)額定剩余電流不大于30mA的RCD,用以在基本防護(hù)失效和/或故障保護(hù)或用電不慎時(shí)的附加防護(hù)措施。
The use of RCDs with a rated residual operating current not exceeding 30 mA, is recognized in a.c. systems as additional protection in the event of failure of the provision for basic protection and/or the provision for fault protection or carelessness by users.
結(jié)論
①擁于保護(hù)人身安全的RCD作為電擊防護(hù)的附加防護(hù)措施,其額定剩余電流動(dòng)作值都不應(yīng)大于30mA。
②國(guó)標(biāo)與IEC標(biāo)準(zhǔn)是一脈相承的!
作者:李炳華(“鳥巢”電氣總設(shè)計(jì)師)
相關(guān)閱讀
◆為何雙極斷路器的相線端子和N線端子不能互換
◆漏電保護(hù)器額定動(dòng)作電流與人體安全電流30mA的關(guān)系